| Product Type |
CJ-series Isolated-type Universal Input Unit |
| Applicable Controller |
CJ / NJ Series
|
| Number of Inputs |
4 channels |
| Input Type (per channel, independently configurable) |
Temperature — Pt100 (JIS/IEC), Pt1000, JPt100; Thermocouple K, J, T, L, R, S, B Voltage — 1–5 V, 0–5 V, 0–10 V Current — 4–20 mA, 0–20 mA
|
| Resolution |
1/12,000 (voltage/current input)
|
| Accuracy (at 25°C, excl. sensor error) |
Voltage/Current: ±0.3% F.S. ±1 digit max. Pt100/Pt1000/JPt100: ±0.3% of PV or ±0.8°C, whichever is greater, ±1 digit max. Thermocouple: ±0.3% of PV or ±1.5°C, whichever is greater, ±1 digit max.
|
| Temperature Coefficient |
±100 ppm/°C max. (F.S.)
|
| Conversion Time |
250 ms / 4 points
|
| Isolation |
Between input channels (isolated) |
| I/O Connection |
Detachable screwless clamp terminal block
|
| Current Consumption (5 V) |
0.32 A
|
| Occupied Unit Numbers |
1 unit number
|
| Mounting Position |
CPU Rack or Expansion Rack
|
| Max. Units Mountable |
40 (within allowable current/power range)
|
| Dimensions (W × H × D) |
31 × 90 × 65 mm |
| Weight |
150 g max. (Taiwan source) / 186 g (EU source)
|
| Degree of Protection |
IP20
|
| Standards |
UC1, L, CE
|