| Product Type |
Digital Temperature Controller (Panel-mount or DIN rail) |
| Control Method |
ON/OFF control, P, PI, PD, or PID control (with auto-tuning)
|
| Input Types |
Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, PL II RTD: Pt100 (DPt100), JPt100, Cu50 Analog: 4–20 mA, 0–20 mA, 1–5 V, 0–5 V, 0–10 V
|
| Display |
7-segment LED (3-digit or 4-digit), single or dual display (PV + SV)
|
| Sampling Cycle |
Typically 100 ms (high-speed models may be faster)
|
| Control Output |
Relay output: SPST-NO or SPDT, 250 VAC, 3 A – 5 A (resistive load) Voltage output (SSR drive): 12 VDC, max. 21 mA Linear current output: 4–20 mA / 0–20 mA, load ≤ 500 Ω
|
| Auxiliary / Alarm Output |
1 to 3 alarm outputs (relay or SSR drive), depending on model
|
| Power Supply Voltage |
AC: 100–240 VAC, 50/60 Hz (universal) AC/DC: 24 VAC / 24 VDC (low-voltage models)
|
| Power Consumption |
Approx. 5–7.5 VA max. (AC models); approx. 1.6–2.3 W max. (DC models)
|
| Display Accuracy (at 23°C ± 5°C) |
RTD / Thermocouple: ±0.5% of PV or ±1°C (whichever is greater), ±1 digit (Accuracy degrades slightly outside room temperature range)
|
| Hysteresis (for ON/OFF control) |
Adjustable, typically 0.1–100°C / °F (or F.S. 0.2–3%)
|
| Proportional Band (P) |
Adjustable, typically 0.1–999.9°C / °F
|
| Integral / Derivative Time (I / D) |
Adjustable, typically 0–9999 seconds
|
| Control Period |
Adjustable, typically 0.5–120.0 seconds
|
| Dielectric Strength |
AC 2 kV (between measurement input and power supply, for AC-powered models)
|
| Operating Temperature |
−10°C to +50°C (standard models)
|
| Operating Humidity |
35–85% RH (non-condensing)
|
| Dimensions (Front Panel) |
Common DIN sizes: 48×48 mm, 96×48 mm, 48×96 mm
|
| Weight (Net) |
Approx. 100 g – 180 g (varies by size and enclosure) |